NSW does not have one fixed septic setback table. The state’s Onsite Wastewater Management Guidelines (NSW Office of Local Government, April 2025) give a buffer range for each feature: 1.5 to 15 m from property boundaries, 2 to 6 m from buildings, 15 to 40 m from farm dams and intermittent creeks, 50 to 100 m from permanent surface water and 15 to 100 m from bores and wells (Table 4-2, p.62). The council picks the figure for a site within that range after a risk assessment, and the distances run from the effluent application area (the trenches, bed or irrigation area), not the tank.
This page is general information. The distances that bind a particular system are the ones in its council approval.
The regulatory framework
Installing, constructing or altering a septic system needs council approval under section 68 of the Local Government Act 1993 (OLG guidelines, p.15). In Port Macquarie-Hastings that approval is lodged through the NSW Planning Portal with a geotechnical wastewater report from a suitably qualified person (PMHC, On-site sewage approvals); the report is where the proposed buffers are set out and justified.
The April 2025 guidelines replace the 1998 state guidelines, Onsite Sewage Management for Single Households (p.10). They say buffers “must be set to suit local conditions”, and that near drinking water extraction areas or oyster aquaculture areas they are set in consultation with the water authority or the NSW Food Authority (p.61). PMHC’s on-site sewage page does not publish its own setback table, so ask the council which figures it applies before a design is drawn. The council approval guide covers the application steps.
Setback distances: septic tank (the tank itself)
The guidelines’ buffer table applies to the effluent application area. For the treatment tank they set a structural rule instead: the base of the tank excavation must sit no closer than a 45 degree line from buildings and site boundaries, and the location should account for odour and noise for people on the site and next door. Treatment systems generally sit downslope of the building they serve (OLG guidelines, p.70).
The tank also has to stay reachable. The guidelines’ model approval conditions require access for monitoring, maintenance and pump-out (condition 16, p.201), which rules out building or paving over the lids.
Setback distances: absorption area (trenches, mounds, irrigation)
Horizontal buffers from the effluent application area, from Table 4-2 of the OLG guidelines (p.62):
| Sensitive receptor | Buffer range |
|---|---|
| Property boundaries | 1.5 to 15 m (OLG) |
| Buildings | 2 to 6 m (OLG) |
| Retaining walls, embankments and cuttings | 3 m or a 45 degree angle from the toe of the wall, whichever is greater (OLG) |
| Drives, paths and walkways | 1.5 to 6 m (OLG) |
| Swimming pools, recreational areas, market gardens | 3 to 15 m (OLG) |
| In-ground water tanks and services (water, electrical, telecommunications, plumbing) | 3 to 15 m (OLG) |
| Permanent surface water bodies | 50 to 100 m (OLG) |
| Intermittent water bodies, farm dams, roadside drainage, drainage depressions, stormwater systems | 15 to 40 m (OLG) |
| Bores and wells | 15 to 100 m (OLG) |
Vertical separation from the base of the application system to groundwater, bedrock or a hardpan is 0.6 to 1.5 m (Table 4-3). Where it is under 0.6 m, the guidelines say the application point should be raised with imported soil or sand to form a raised bed or mound (p.63).
For a potable bore, a buffer below the range must be justified by viral die-off modelling (Table 4-2, note 4). Separately, where an on-site system is within 250 m, DCCEEW and WaterNSW limit applications for new groundwater bores (p.69). The bore distances guide and the waterway buffer guide go into those two receptors in more detail.
Older figures still circulate. NSW’s Easy Septic Guide (NSW Department of Local Government, 2000) recommended, for example, 100 m to permanent surface waters, 250 m to a domestic bore and 40 m to farm dams. Those were recommendations under the old framework; a design today is assessed against the 2025 ranges and the council’s own policy.
What pushes a buffer to the top of the range
Table 4-4 of the OLG guidelines (pp.63-69) sets out what moves each buffer from the low end to the high end:
- Effluent quality. Secondary treated, disinfected effluent under a service contract sits at the low end; primary treated effluent from a septic tank sits at the high end.
- How it is applied. Subsurface or subsoil application is lower risk than surface or above-ground application, and buffers “should be at the upper end” of the range for any surface application (p.61).
- Slope. For subsurface application, 0 to 10% is low constraint and over 30% is high (OLG, p.63).
- Flood potential and drainage. Land below the 1 in 20 year flood contour, visible seepage, moisture-tolerant vegetation or a low-lying position push the buffer up.
- Soils and geology. Gravel aquifers, fractured rock and very permeable or very poorly draining soil categories push bore and groundwater buffers up.
Setbacks on small lots: where it gets difficult
On a tight lot the ranges can collide. The guidelines allow two specific relaxations (OLG, p.62): subsurface drip irrigation of at least secondary treated effluent downslope of an upslope boundary may come within 0.5 m of that boundary, and on existing lots the buffer to recreational areas may be removed if there is no alternative and subsurface application of at least secondary treated effluent is used. Other reductions need a risk-based assessment; the guidelines’ worked example cuts a buffer to an intermittent creek from 40 m to 30 m using viral die-off modelling (Appendix A6.5, p.246).
Subdivision is where this is tested first. The subdivision guide explains how effluent areas are shown on each proposed lot.
Setbacks and neighbouring properties
The boundary buffer applies to every boundary, and the guidelines list sensitive receptors “both on and off the site” (p.61). A neighbour’s bore, dam or pool near the shared fence therefore counts in the assessment even though it is on another title. The same applies in reverse when the neighbour designs a system.
Frequently asked questions
Do setback distances apply to the septic tank lid or to the edge of the tank?
The buffer table measures from the effluent application area: the guidelines define a buffer distance as the separation between that area and a sensitive receptor or feature such as a boundary (OLG, p.176). The tank is governed by the 45 degree excavation rule and access, so confirm with the designer how the council measures it.
What if my existing system is closer than the minimum setback?
The guidelines say an existing system “does not need to meet any revised standards” introduced since it was installed, provided it meets the performance standards in the Regulation (OLG, p.40). Altering or replacing it needs a new section 68 approval, assessed against current requirements. A septic inspection shows how the system is performing.
Can I get a variation to the minimum setback distance?
The guidelines recommend councils set buffers conservatively and allow reductions “only” where modelling such as viral die-off or nutrient attenuation shows the standard buffer is unnecessarily conservative (OLG, p.61). Whether PMHC accepts a reduction is the council’s decision on the report submitted.
Does the setback apply to AWTS spray irrigation differently?
Yes. Surface application, which includes spray irrigation, sits at the high-constraint end of every buffer range, and the guidelines say buffers should be at the upper end of the range for any surface application (OLG, p.61). Subsurface drip irrigation of secondary treated effluent sits at the low end.
Request a quote to have a contractor check where an existing system sits and how it is performing.